SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
387
2 Parameters
2.2 List of parameters
Example:
In order that for a Quick Stop (OFF3) the fixed torque limit is effective, binector input: p1551 must be interconnected
to r0899.5.
Description: Sets the signal source for the scaling of the upper torque limiting to limit the speed controller output without taking
into account the current and power limits.
Description: Sets the scaling of the stall limit for the start of field weakening.
Danger: If the stall current limit is increased, then the q current setpoint can exceed the stall limit; as a consequence, a
hysteresis effect can occur when loading and unloading.
Description: Sets the signal source for the scaling of the lower torque limiting to limit the speed controller output without taking into
account the current and power limits.
Description: Sets the signal source for the motoring and negative regenerative power limit.
Dependency: Refer to: p1530, p1531
Note: The resulting motoring power limit is the minimum from p1530 and the signal which is read in.
The resulting regenerative power limit is the maximum from p1531 and the negative signal which is read in.
p1552[0...n] CI: Torque limit upper scaling without offset / M_max up w/o offs
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6060
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 1
p1553[0...n] Stall limit scaling / Stall limit scal
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
80.0 [%] 130.0 [%] 100.0 [%]
p1554[0...n] CI: Torque limit lower scaling without offset / M_max low w/o offs
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6060
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- - 1
p1555[0...n] CI: Power limit / P_max
VECTOR_G (n/M) Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 6640
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: r2004 Expert list: 1
Min Max Factory setting
- - 1