SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
223
2 Parameters
2.2 List of parameters
Description: Sets the reduction factor for the overtemperature of the thermal adaptation of the stator/rotor resistance.
The value is a starting value when switching on. Internally, after switch-on, the reduction factor has no effect
corresponding to the thermal time constant.
Dependency: Refer to: p0610
Note: The reduction factor is only effective for p0610 = 12, and refers to the overtemperature.
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature model 1 (I2t).
- Fault F07011 is output after the fault threshold is exceeded.
- fault threshold for r0034 = 100 % * (p0615 - 40) / (p0605 - 40).
Dependency: The parameter is only used for permanent-magnet synchronous motors (p0300 = 2xx).
Refer to: r0034, p0611, p0612
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: The hysteresis is 2 K.
Description: Sets the alarm threshold 1 for monitoring the motor temperature.
Note: The alarm threshold is not, as for p0604, coupled to the timer p0606. The hysteresis for canceling the fault is 2 K.
Description: Sets the thermal adaptation of the stator/primary section resistance and rotor/secondary section resistance according
to r0395 and r0396.
Value: 0: No thermal adaptation of stator and rotor resistances
1: Resistances adapted to the temperatures of the thermal model
2: Resistances adapted to the measured stator winding temperature
p0614[0...n] Thermal resistance adaptation reduction factor / Therm R_adapt red
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [%] 100 [%] 30 [%]
p0615[0...n] Mot_temp_mod 1 (I2t) fault threshold / I2t F thresh
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 220.0 [°C] 180.0 [°C]
p0616[0...n] Motor overtemperature alarm threshold 1 / Mot temp alarm 1
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: 21_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [°C] 200.0 [°C] 130.0 [°C]
p0620[0...n] Thermal adaptation, stator and rotor resistance / Mot therm_adapt R
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_ALL Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1