SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
593
2 Parameters
2.2 List of parameters
Description: Display and BICO output for the status word of the essential service mode (ESM).
Note: ESM: Essential Service Mode
Description: Exits the quick commissioning (p0010 = 1) with automatic calculation of all of the parameters that depend on the
entries made during the quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning. The interconnections of
PROFIBUS PZD telegram selection (p0922) and the interconnections via p0700 are re-established and all of the
dependent filter and closed-loop control parameters are calculated (corresponding to p0340 = 1).
p3900 = 2 includes the restoration of the interconnections of PROFIBUS PZD telegram selection (p0922) and the
interconnections via p0700 and the calculations corresponding to p0340 = 1.
p3900 = 3 only includes the end of quick commissioning.
Value: 0: No quick parameterization
1: Quick parameterization after parameter reset
2: Quick param. (only) for controller par. and reset for BICO par
3: Completion of quick commissioning
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: When the calculations have been completed, p3900 and p0010 are automatically reset to a value of zero.
Description: Exits quick commissioning (p0010 = 1) with automatic calculation of all parameters of all existing drive data sets that
depend on the entries made during quick commissioning.
p3900 = 1 initially includes a parameter reset (factory setting, the same as p0970 = 1) for all parameters of the drive
object; however, without overwriting the entries made during the quick commissioning.
r3889.0...10 CO/BO: ESM status word / ESM ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 7033
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Essential service mode (ESM) activated Yes No -
01 Direction of rotation inverted Yes No -
02 Setpoint signal lost Yes No -
07 Setpoint TB30/TM31 analog input
parameterized (p3886)
Yes No -
08 Power unit not permissible (permissible
p0201 >= 14000)
Yes No -
09 Response OFF1/OFF2 activated Yes No -
10 Automatic restart interrupted (F07320) Yes No -
p3900 Completion of quick commissioning / Compl quick_comm
B_INF Can be changed: C2(1) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0
p3900 Completion of quick commissioning / Compl quick_comm
VECTOR_G Can be changed: C2(1) Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 3 0