SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
121
2 Parameters
2.2 List of parameters
Description: Displays the status word of the automatic motor parameter sensing of a motor with DRIVE-CLiQ.
Motor parameter sensing takes place in the following events if the SMI is connected to the Motor Module and the
encoder is activated (p0145):
- Warm restart
- downloading projects.
- POWER ON (off/on).
- where p0300 = 10000, 10001.
Dependency: Refer to: p0145, p0300
Note: SMI: SINAMICS Sensor Module Integrated
Description: Sets the rated motor voltage (rating plate).
Dependency: Refer to: p0349
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Description: Sets the rated motor current (rating plate).
Dependency: Refer to: p0349
Notice: When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly. This is not the case when commissioning the motor (p0010 = 3).
If the rated motor current exceeds twice the maximum drive converter current (r0209), then the maximum current is
reduced due to the current harmonics that increase overproportionally (r0067).
Note: When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
r0303[0...n] Motor with DRIVE-CLiQ status word / Motor w DQ ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor data set selected MDS1 MDS0 -
01 Motor connection type Delta Star -
02 Windings can be changed Yes No -
03 Windings can be changed number 2 0 -
p0304[0...n] Rated motor voltage / Mot U_rated
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6301, 6724
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [Vrms] 20000 [Vrms] 0 [Vrms]
p0305[0...n] Rated motor current / Mot I_rated
VECTOR_G Can be changed: C2(1, 3) Calculated: - Access level: 1
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6301
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [Arms] 10000.00 [Arms] 0.00 [Arms]