2 Parameters
2.2 List of parameters
SINAMICS G130/G150
958 List Manual (LH2), 04/2014, A5E03263479A
5: Siemens internal
6: Siemens internal
Dependency: The functions in p9938 can only be set for p9937.0 = 0.
Refer to: r9936, p9937, p9939, p9942
Notice: If value = 0:
- detailed diagnostics is inactive.
- the error counter is active (r9936).
If value > 0:
- the error counter is inactive (r9936).
- the detailed diagnostics as configured is active (r9943).
Description: Sets the time interval for recording the error counter in r9943.
Dependency: Refer to: r9936, p9938, p9942, r9943
Description: For p9941 =1, the serial numbers of all components in the target topology are deleted (zero is written).
Through activation and de-activation this enables the actual topology components to be newly assigned to the target
topology components.
Note: p9941 is automatically set to 0 at the end of the operation.
A warm restart is triggered automatically after p0009 = 0.
Description: Sets the component, whose feeder cable is monitored for data transfer errors.
The feeder cable is the DRIVE-CLiQ cable that is connected to a component in the direction of the Control Unit.
Errors that have occurred in the selected time interval (p9939) can be read-out from r9943.
Dependency: Refer to: r9936, p9938, p9939, r9943
p9939 DRIVE-CLiQ detailed diagnostics time interval / DQ detail t_interv
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 [s] 3600 [s] 1 [s]
p9941 Target topology feature delete all components / Feature delete
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: C1(1) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Topology Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0 1 0
p9942 DRIVE-CLiQ detailed diagnostics select individual connection / DQ detail conn
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0