2 Parameters
2.2 List of parameters
SINAMICS G130/G150
698 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for trigger 2 of the recorder.
Trigger 2.1 is formed by ANDing the signal source in p6994[0] and the bit mask in p6993[0].
Trigger 2.2 is formed by ANDing the signal source in p6994[1] and the bit mask in p6993[1].
Trigger 2.3 is formed by ANDing the signal source in p6994[2] and the bit mask in p6993[2].
Index: [0] = Trigger 2.1
[1] = Trigger 2.2
[2] = Trigger 2.3
Dependency: Refer to: p6993
Description: Setting to parameterize the signals for the recorder.
Description: Displays the state of the sequencer for the recorder.
Value: 0: Not active
10: Active
20: Post trigger time running
30: Prepare data save operation
40: Start data save
50: End data save
60: Configuration
Description: Sets the signal sources to activate and trigger the recorder.
Index: [0] = Activating
[1] = Trigger 1.1
[2] = Trigger 1.2
[3] = Trigger 1.3
[4] = Trigger 1.4
p6994[0...2] CI: Recorder trigger 2 signal source / Rec trig 2 S_src
B_INF (Recorder),
VECTOR_G
(Recorder)
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 / Integer32 Dyn. index: - Func. diagram: 8144
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p6996[0...63] Recorder signals / Rec sig
B_INF (Recorder),
VECTOR_G
(Recorder)
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: 8144
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 996553699 0
r6997 CO: Recorder sequencer state / Rec state
B_INF (Recorder),
VECTOR_G
(Recorder)
Can be changed: - Calculated: - Access level: 4
Data type: Integer16 Dyn. index: - Func. diagram: 8144
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 60 -
p6998[0...4] BI: Recorder trigger 1 signal sources / Rec trig 1 S_src
B_INF (Recorder),
VECTOR_G
(Recorder)
Can be changed: U, T Calculated: - Access level: 4
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 8144
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0