2 Parameters
2.2 List of parameters
SINAMICS G130/G150
252 List Manual (LH2), 04/2014, A5E03263479A
Note: A motor is only changed over (a new motor selected) after the pulses have been suppressed.
When the motor data sets are changed over, the following applies:
Bit numbers that are not identical, signify that the motor must be changed over.
Description: Sets the signal source for the feedback signal when changing over the motor.
For p0833.0 = 1 the following applies:
This feedback signal (0/1 edge) is required after a motor changeover to enable the pulses.
Dependency: Refer to: p0833
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Displays the status word of the motor changeover.
These signals can be connected to digital outputs to change over the motor.
Dependency: Refer to: p0827
Description: Sets the signal source for the feedback signal of the contactors when changing over motors.
There is a fixed inter-relationship between energizing the contactor and the feedback signal.
p0828[0...n] BI: Motor changeover feedback signal / Mot_chng fdbk sig
VECTOR_G Can be changed: C2(3), T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: 8575
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r0830.0...15 CO/BO: Motor changeover status word / Mot_chngov ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: - Func. diagram: 8575
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Motor selection bit 0 High Low -
01 Motor selection bit 1 High Low -
02 Motor selection bit 2 High Low -
03 Motor selection bit 3 High Low -
04 Motor selection bit 4 High Low -
05 Motor selection bit 5 High Low -
06 Motor selection bit 6 High Low -
07 Motor selection bit 7 High Low -
08 Motor selection bit 8 High Low -
09 Motor selection bit 9 High Low -
10 Motor selection bit 10 High Low -
11 Motor selection bit 11 High Low -
12 Motor selection bit 12 High Low -
13 Motor selection bit 13 High Low -
14 Motor selection bit 14 High Low -
15 Motor selection bit 15 High Low -
p0831[0...15] BI: Motor changeover contactor feedback / Mot_chg cont fdbk
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 8575
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0