SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
563
2 Parameters
2.2 List of parameters
Description: Sets the time constant for the PT1 element to smooth the torque actual value.
The smoothed torque actual value is compared with the threshold values and is only used for messages and signals.
Description: Sets the monitoring time for phase failure detection of the motor.
Notice: After the value has been modified, no further parameter modifications can be made and the status is shown in r3996.
Modifications can be made again when r3996 = 0.
Note: Monitoring is only effective for blocksize and booksize power units.
For p3235 = 0 the function is deactivated.
For VECTOR, the following applies:
The monitoring is automatically de-activated during the flying restart operation for a motor that is still rotating.
Description: Sets the speed threshold value for the signal "speed deviation model/external" (BO: r2199.7).
Dependency: Refer to: r1443, r2169, r2199, p3237
Description: Sets the hysteresis speed for the signal "speed deviation model/external" (BO: r2199.7).
Dependency: Refer to: r2199, p3236
p3233[0...n] Torque actual value filter time constant / M_act_filt T
VECTOR_G (Ext msg) Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8013
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000000 [ms] 0 [ms]
p3235 Phase failure signal motor monitoring time / Ph_fail t_monit
VECTOR_G Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 2000 [ms] 320 [ms]
p3236[0...n] Speed threshold 7 / n_thresh val 7
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 3000.00 [rpm] 100.00 [rpm]
p3237[0...n] Hysteresis speed 7 / n_hysteresis 7
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 8012
P-Group: Messages Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 200.00 [rpm] 2.00 [rpm]