For p4117 = 1, the following applies:
For a sensor error, for the maximum value, minimum value and average value of the corresponding group, a value of
-300 °C is output.
Value: 0: Skip sensor
1: Output value = -300 °C
Index: [0] = Group 0
[1] = Group 1
[2] = Group 2
Dependency: Refer to: r4105, p4111, r4112, r4113, r4114
Description: Sets the hysteresis for the fault threshold/alarm threshold (p4102[0...23]) for the Terminal Module 150 (TM150).
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency: Refer to: p4102, p4103, r4104, r4105
Note: The following applies for a corresponding alarm:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x] -
hysteresis (p4118[x]).
The following applies for a corresponding fault:
- Remains until the temperature actual value (r4105[x]) reaches or falls below the threshold value (p4102[2x+1]) -
hysteresis (p4118[x]) and the fault has been acknowledged.
Description: Setting to activate/deactivate the filter to smooth the temperature signal for the Terminal Module 150 (TM150).
The smoothing is realized with a 1st order lowpass filter
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
Value: 0: Filter deactivated
1: Filter activated
Index: [0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
p4118[0...11] TM150 fault threshold/alarm threshold hysteresis / TM150 thresh hyst
TM150 Can be changed: T Calculated: - Access level: 1
Data type: Unsigned16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [K] 50 [K] 5 [K]
p4119[0...11] TM150 activate/deactivate smoothing / TM150 smooth act
TM150 Can be changed: T Calculated: - Access level: 1
Data type: Integer16 Dyn. index: - Func. diagram: 9626, 9627
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0