SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
755
2 Parameters
2.2 List of parameters
Note: Corresponds to the CANopen object 1200 hex.
SDO: Service Data Object
Description: Displays the Pre-defined Error Field of the CAN node.
It includes the number of all errors that have occurred, the number of errors that have occurred for each drive and the
errors according to their history.
The first 16 bits represent the CANopen error code and the second 16 bits the SINAMICS error code.
Index 1 has the same structure - however, the drive object ID is in the second 16 bits instead of the SINAMICS error
code.
CANopen error code:
0000 hex: No error present.
8110 hex: Alarm A08751 present.
8120 hex: Alarm A08752 present.
8130 hex: Alarm A08700(F) with alarm value = 2 present.
1000 hex: Generic error 1 present (there is at least one fault outside the range 8700 ... 8799)
1001 hex: Generic error 2 present (there is at least one alarm in the range 8700 ... 8799 with the exception of
A08751, A08752, A08700)
All drive objects are acknowledged by writing the value 0 to index 0. As soon as a fault has been acknowledged or an
alarm cleared, then it is also cleared from the fault list.
p8611[0...82] CAN Pre-defined Error Field / Pre_def err field
CU_G130_DP (CAN),
CU_G130_PN (CAN),
CU_G150_DP (CAN),
CU_G150_PN (CAN)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF 1000 hex 0000 hex