SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
145
2 Parameters
2.2 List of parameters
Description: Displays the magnetizing inductance of the motor.
For separately-excited synchronous motors:
Displays the saturated magnetizing inductance in the rotor direction (d-axis).
Note: The parameter is not used for synchronous motors (p0300 = 2xx).
Description: Displays the saturated magnetizing inductance of a separately-excited synchronous motor quadrature to the rotor
direction (q axis).
Description: Displays the rotor time constant.
For separately-excited synchronous motors:
Displays the damping time constant to the rotor direction (d axis).
Note: The parameter is not used for synchronous motors.
The value is calculated from the total of the inductances on the rotor side (p0358, p0360) divided by the
rotor/damping resistance (p0354). The temperature adaptation of the rotor resistance for induction motors is not
taken into account.
Description: Displays the damping time constant of a separately-excited synchronous motor quadrature to the rotor direction (q
axis).
Note: The value is calculated from the total of the inductances on the damping side (p0359, p0361) divided by the damping
resistance (p0355).
r0382[0...n] Motor magnetizing inductance transformed / Lh d axis saturated / Mot L_m tr/Lhd sat
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]
r0383[0...n] Motor magnetizing inductance q axis saturated / Mot L_magn q sat
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: 15_1 Unit selection: p0349
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [mH] - [mH] - [mH]
r0384[0...n] Motor rotor time constant / damping time constant d axis / Mot T_rotor/T_Dd
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 6722
P-Group: Motor Units group: - Unit selection: -
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [ms] - [ms] - [ms]
r0385[0...n] Motor damping time constant q axis / Mot L_damping q
VECTOR_G Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: -
P-Group: Motor Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
- [ms] - [ms] - [ms]