SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
65
2 Parameters
2.2 List of parameters
Description: Displays the actual modulation depth.
Dependency: Refer to: r0028
Note: For space vector modulation, 100% corresponds to the maximum output voltage without overcontrol.
Values above 100 % indicate an overcontrol condition - values below 100% have no overcontrol.
The phase voltage (phase-to-phase, rms) is calculated as follows:(r0074 x r0070) / (sqrt(2) x 100 %).
The modulation depth is available smoothed (r0028) and unsmoothed (r0074).
Description: Display and connector output for the field-generating current setpoint (Id_set).
Note: This value is irrelevant for the U/f control mode.
Description: Display and connector output for the field-generating current actual voltage (Id_act).
Dependency: Refer to: r0029
Note: This value is irrelevant for the U/f control mode.
The field-generating current actual value is available smoothed (r0029) and unsmoothed (r0076).
Description: Display and connector output for the torque/force-generating current setpoint.
Note: This value is irrelevant for the U/f control mode.
r0074 CO: Modulat_depth / Modulat_depth
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 5730, 6730,
6731, 6799, 8940, 8950
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
r0075 CO: Current setpoint field-generating / Id_set
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6700, 6714,
6725
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0076 CO: Current actual value field-generating / Id_act
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 5700, 5714,
5730, 6700, 6714, 6799
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0077 CO: Current setpoint torque-generating / Iq_set
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6700, 6710
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]