2 Parameters
2.2 List of parameters
SINAMICS G130/G150
668 List Manual (LH2), 04/2014, A5E03263479A
Description: Displays the trace buffer (record buffer) for trace 0 and signal 0 as integer number.
Note: For signals, data type I32 or U32, the trace buffer is assigned as follows:
r4760[0] = value 0
r4760[1] = value 1
...
r4760[8191] = value 8191
For signals, data type I16 or U16, the trace buffer is assigned as follows:
r4760[0] = value 1 (bit 31 ... 16) and value 0 (bit 15 ... 0)
r4760[1] = value 3 (bit 31 ... 16) and value 2 (bit 15 ... 0)
...
r4760[8191] = value 16383 (bit 31 ... 16) and value 16382 (bit 15 ... 0)
For signals, data type I8 or U8, the trace buffer is assigned as follows:
r4760[0] = value 3 (bit 31 ... 24) value 2 (bit 23 ... 16) value 1 (bit 15 ... 8) value 0 (bit 7 ... 0)
r4760[1] = value 7 (bit 31 ... 24) value 6 (bit 23 ... 16) value 5 (bit 15 ... 8) value 4 (bit 7 ... 0)
...
r4760[8191] = value 32767 (bit 31 ... 24) value 32766 (bit 23 ... 16) value 32765 (bit 15 ... 8) value 32764 (bit 7 ... 0)
Description: Displays the trace buffer (record buffer) for trace 0 and signal 1.
Dependency: Refer to: r4760
Description: Displays the trace buffer (record buffer) for trace 0 and signal 2.
Dependency: Refer to: r4760
Description: Displays the trace buffer (record buffer) for trace 0 and signal 3.
r4760[0...16383] Trace 0 trace buffer signal 0 / Trace 0 tr sig 0
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
r4761[0...16383] Trace 0 trace buffer signal 1 / Trace 0 tr sig 1
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
r4762[0...16383] Trace 0 trace buffer signal 2 / Trace 0 tr sig 2
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -
r4763[0...16383] Trace 0 trace buffer signal 3 / Trace 0 tr sig 3
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
- - -