2 Parameters
2.1 Overview of parameters
SINAMICS G130/G150
22 List Manual (LH2), 04/2014, A5E03263479A
Calculated
Specifies whether the parameter is influenced by automatic calculations.
The calculation attribute defines which activities influence the parameter.
The following attributes apply:
CALC_MOD_ALL
p0340 = 1
Project download with commissioning software and send from p0340 = 3
CALC_MOD_CON
p0340 = 1, 3, 4
CALC_MOD_EQU
p0340 = 1, 2
CALC_MOD_LIM_REF
p0340 = 1, 3, 5
p0578 = 1
CALC_MOD_REG
p0340 = 1, 3
Access level
Specifies the minimum access level required to be able to display and change the relevant
parameter. The required access level can be set using p0003.
The system uses the following access levels:
1: Standard
2: Extended
3: Expert
4: Service
Parameters with this access level are password protected.
Note
For p3900 > 0, p0340 = 1 is also called automatically.
After p1910 = 1, p0340 = 3 is also called automatically.
Note
Parameter p0003 is CU-specific (belongs to the Control Unit).
A higher access level will also include the functions of the lower levels.