2 Parameters
2.2 List of parameters
Description: Sets the input mode for the safety digital inputs (F-DI).
Note: Only an NC contact can be connected for the safety digital inputs not listed.
Description: Enable signal for the integration of F-DI in the test (forced checking procedure) of the sensor power supply.
Note: F-DI: Failsafe Digital Input
Description: Sets the signal sources for F-DO 0.
The 6 signal sources in p10042[0...5] are AND'ed and the result is output at F-DO 0.
04 SLS_active Selected Not selected -
05 SDI_pos_active Selected Not selected -
06 SDI_neg_active Selected Not selected -
07 SLP_active Selected Not selected -
p10040 SI TM54F F-DI input mode / SI F-DI inp_mode
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0, DI 1+ (X521.3) NO contact NC contact 2850
01 F-DI 1, DI 3+ (X521.5) NO contact NC contact 2850
02 F-DI 2, DI 5+ (X522.2) NO contact NC contact 2850
03 F-DI 3, DI 7+ (X522.4) NO contact NC contact 2850
04 F-DI 4, DI 9+ (X522.6) NO contact NC contact 2850
05 F-DI 5, DI 11+ (X531.3) NO contact NC contact 2851
06 F-DI 6, DI 13+ (X531.5) NO contact NC contact 2851
07 F-DI 7, DI 15+ (X532.2) NO contact NC contact 2851
08 F-DI 8, DI 17+ (X532.4) NO contact NC contact 2851
09 F-DI 9, DI 19+ (X532.6) NO contact NC contact 2851
p10041 SI TM54F F-DI enable for test / SI F-DI enab test
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2848
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 F-DI 0, power supply L1+ Test active No test -
01 F-DI 1, power supply L1+ Test active No test -
02 F-DI 2, power supply L1+ Test active No test -
03 F-DI 3, power supply L1+ Test active No test -
04 F-DI 4, power supply L1+ Test active No test -
05 F-DI 5, power supply L2+ Test active No test -
06 F-DI 6, power supply L2+ Test active No test -
07 F-DI 7, power supply L2+ Test active No test -
08 F-DI 8, power supply L2+ Test active No test -
09 F-DI 9, power supply L2+ Test active No test -
p10042[0...5] SI TM54F F-DO 0 signal sources / SI F-DO 0 S_src
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: 2857
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 783 0