2 Parameters
2.2 List of parameters
SINAMICS G130/G150
226 List Manual (LH2), 04/2014, A5E03263479A
Description: Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency: For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency: For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
Description: Defines the rated overtemperature of the squirrel cage rotor referred to ambient temperature.
Dependency: For 1LA5 and 1LA7 motors (p0300 = 15, 17), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Notice: When selecting a standard induction motor listed in the catalog (p0300 > 100, p0301 > 10000), this parameter is
automatically preassigned and is write protected. Information in p0300 should be carefully observed when removing
write protection.
Note: When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (p0300).
p0626[0...n] Motor overtemperature, stator core / Mot T_over core
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: 21_2 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
10 [K] 200 [K] 50 [K]
p0627[0...n] Motor overtemperature, stator winding / Mot T_over stator
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: 21_2 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
15 [K] 200 [K] 80 [K]
p0628[0...n] Motor overtemperature rotor winding / Mot T_over rotor
VECTOR_G Can be changed: C2(3), U, T Calculated: CALC_MOD_EQU Access level: 3
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Motor Units group: 21_2 Unit selection: p0505
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
20 [K] 200 [K] 100 [K]