EasyManua.ls Logo

Siemens SINAMICS G150 - Flux Outside Tolerance Delay Time; Flux N Tol T_Del; Zero Current Signal Threshold Value; I_0_Sig Thresh; Zero Current Signal Hysteresis; I_0_Sig Hyst; Zero Current Signal Delay Time; I_0_Sig T_Del

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
562 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the delay time for the "flux outside tolerance" message for the flux monitoring.
Dependency: Refer to: p3204, p3205
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
Description: Sets the threshold value for the zero current signal for the zero current monitoring.
If the absolute current falls below the threshold value then r2199.6 is set to 1 after the delay time has expired. The bit
is reset if the threshold value and the hysteresis are exceeded again.
Dependency: Refer to: r2199, p3208, p3209
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description: Sets the hysteresis for the zero current signal for the zero current monitoring.
Dependency: Refer to: p3207, p3209
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description: Sets the delay time for the zero current signal for the zero current monitoring.
Dependency: Refer to: p3207, p3208
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
p3206[0...n] Flux outside tolerance delay time / Flux n tol t_del
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 10.0 [s] 5.0 [s]
p3207[0...n] Zero current signal threshold value / I_0_sig thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.01 [Arms] 10000.00 [Arms] 1.00 [Arms]
p3208[0...n] Zero current signal hysteresis / I_0_sig hyst
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.01 [Arms] 10000.00 [Arms] 1.00 [Arms]
p3209[0...n] Zero current signal delay time / I_0_sig t_del
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 10.00 [s] 0.02 [s]

Table of Contents

Other manuals for Siemens SINAMICS G150

Related product manuals