2 Parameters
2.2 List of parameters
SINAMICS G130/G150
562 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the delay time for the "flux outside tolerance" message for the flux monitoring.
Dependency: Refer to: p3204, p3205
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
Description: Sets the threshold value for the zero current signal for the zero current monitoring.
If the absolute current falls below the threshold value then r2199.6 is set to 1 after the delay time has expired. The bit
is reset if the threshold value and the hysteresis are exceeded again.
Dependency: Refer to: r2199, p3208, p3209
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description: Sets the hysteresis for the zero current signal for the zero current monitoring.
Dependency: Refer to: p3207, p3209
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold value in p2161 (r2199.0 = 1).
Description: Sets the delay time for the zero current signal for the zero current monitoring.
Dependency: Refer to: p3207, p3208
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The monitoring is only carried out for speeds less than the speed threshold in p2161 (r2199.0 = 1).
p3206[0...n] Flux outside tolerance delay time / Flux n tol t_del
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 10.0 [s] 5.0 [s]
p3207[0...n] Zero current signal threshold value / I_0_sig thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.01 [Arms] 10000.00 [Arms] 1.00 [Arms]
p3208[0...n] Zero current signal hysteresis / I_0_sig hyst
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: 6_2 Unit selection: p0505
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.01 [Arms] 10000.00 [Arms] 1.00 [Arms]
p3209[0...n] Zero current signal delay time / I_0_sig t_del
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [s] 10.00 [s] 0.02 [s]