2 Parameters
2.2 List of parameters
Note: Re bit 00 ... 09:
Used to control internal sequences during the flying restart.
Depending on the motor type (p0300), the number of active bits differs.
Re bits 10 ... 17:
Are used to monitor the flying restart sequence.
Description: Sets faults for which automatic restart should not be effective.
Dependency: The setting is only effective for p1210 = 6, 16.
Refer to: p1210
Description: Modifies the pre-charging monitoring of the infeed.
The active automatic restart (AR) of the following drive object can be interconnected using this binector input (BI:
p1207 = r1214.2).
This means that when the automatic restart is operational, the pre-charging monitoring of the infeed is de-activated
and is only re-activated under the following conditions:
- the absolute current in the DC link is greater than 2 % of the maximum current (r0209) of the infeed to provide
protection against short-circuit in the DC link.
- if a Voltage Sensing Module (VSM) is being used, the line supply voltage amplitude is greater than 3 % of the
parameterized unit supply voltage (p0210) to protect the pre-charging resistors against continuous filter current when
the line supply partially returns.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Speed adaptation circuit record angle Yes No -
01 Speed adaptation circuit set gain to 0 Yes No -
02 Isd channel enable Yes No -
03 Speed control switched out Yes No -
04 Quadrature arm switched in Yes No -
05 Special transformation active Yes No -
06 Speed adaptation circuit set I comp to 0 Yes No -
07 Current control on Yes No -
08 Isd_set = 0 A Yes No -
09 Frequency held Yes No -
10 Search in the positive direction Yes No -
11 Search Started Yes No -
12 Current impressed Yes No -
13 Search interrupted Yes No -
14 Speed adaptation circuit deviation = 0 Yes No -
15 Speed control activated Yes No -
16 Fast flying restart w/ voltage model for
induction motor activ.
Yes No -
17 Fast flying restart w/ voltage model for
induction motor exited
Yes No -
18 Apply VSM voltage to the monitor Yes No -
19 Preassign flux ramp Yes No -
20 Adaptation current controller and speed
adapt. controller gain
Yes No -
p1206[0...9] Faults without automatic restart / F w/out auto AR
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 65535 0
p1207 BI: AR connection following drive object / AR connection DO
B_INF Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0