4 Faults and alarms
4.1 Overview of faults and alarms
SINAMICS G130/G150
1266 List Manual (LH2), 04/2014, A5E03263479A
4.1 Overview of faults and alarms
4.1.1 General information on faults and alarms
Display of faults/alarms (messages)
In the case of a fault, the drive signals the corresponding fault(s) and/or alarm(s).
For example, the following methods for displaying faults and alarms are available:
Display via the fault and alarm buffer with PROFIBUS/PROFINET.
Display online using the commissioning software.
Differences between faults and alarms
The differences between faults and alarms are as follows:
Table 4-1 Differences between faults and alarms
Type Description
Faults What happens when a fault occurs?
The appropriate fault reaction is triggered.
Status signal ZSW1.3 is set.
The fault is entered in the fault buffer.
How are faults eliminated?
Remove the original cause of the fault.
Acknowledge the fault.
Alarms What happens when an alarm occurs?
Status signal ZSW1.7 is set.
The alarm is entered in the alarm buffer.
How are alarms removed?
Alarms acknowledge themselves. If the cause of the alarm is no longer
present, they automatically reset themselves.