SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
693
2 Parameters
2.2 List of parameters
Description: Displays the alarm threshold for monitoring the motor temperature for motor temperature model 3.
This value is used to calculate the utilization display (p0034).
The parameter value is an image of p5390.
Note: Users cannot see and change parameter p5390 (only Siemens internal).
Description: Sets the fault threshold for monitoring the motor temperature for motor temperature model 3.
Fault F07011 is output after the fault threshold is exceeded.
The parameter value is an image of p5391.
Note: Users cannot see and change parameter p5391 (only Siemens internal).
Description: Displays the PROFIenergy mode ID of the effective energy saving mode.
Value: 0: POWER OFF
2: Energy-saving mode 2
255: Ready
Note: Pe: PROFIenergy profiles
Description: Sets the minimum possible pause time for the energy-saving mode.
The value is the sum of the following times:
- Energy-saving mode transition time
- Operating state transition time regular
- Energy-saving mode, dwell time minimal
Index: [0] = Reserved
[1] = Mode 2
r5398[0...n] Mot_temp_mod 3 alarm threshold image p5390 / A thr image p5390
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r5399[0...n] Mot_temp_mod 3 fault threshold image p5391 / F thr image p5391
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: MDS, p0130 Func. diagram: 8017
P-Group: Displays, signals Units group: 21_1 Unit selection: p0505
Not for motor type: ASM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
- [°C] - [°C] - [°C]
r5600 Pe energy saving mode ID / Pe mode ID
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 -
p5602[0...1] Pe energy-saving mode pause time minimal / Pe mod t_pause min
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2381
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
300000 [ms] 4294967295 [ms] [0] 300000 [ms]
[1] 480000 [ms]