2 Parameters
2.2 List of parameters
SINAMICS G130/G150
340 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for the feedback signal "synchronization completed" for the bypass function.
Dependency: Refer to: r3819
Description: Sets the signal source for the feedback signal of the bypass switch.
Index: [0] = Switch motor/drive
[1] = Switch motor/line supply
Note: In the case of switches without a feedback signal, interconnect the corresponding control bit as the signal source:
BI: p1269[0] = r1261.0
BI: p1269[1] = r1261.1
Description: Sets the maximum search frequency for a flying restart in an inhibited setpoint direction (p1110, p1111).
Note: The parameter has no effect for an operating mode, which only searches in the setpoint direction (p1200 > 3).
Description: In the simulation mode, the closed-loop control or U/f control can be operated without motor.
The simulation mode is used to test the power unit. Even though the DC link voltage is missing, the pulses are
enabled when powering up. The DC link pre-charging is bypassed and the undervoltage detection is disabled.
Closed-loop speed control with an encoder is possible if the torque setpoint (r0079) is used in order to operate a
second drive in the closed-loop torque controlled mode.
Value: 0: OFF
1: ON
Dependency: The following functions are de-activated in the simulation mode:
- motor data identification routine
- motor data identification routine, rotating without encoder
- pole position identification
p1268 BI: Bypass feedback synchronization completed / FS sync compl
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 3819.2
p1269[0...1] BI: Bypass switch feedback signal / Bypass FS
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p1271[0...n] Flying restart maximum frequency for the inhibited direction / FlyRes f_max dir
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [Hz] 650 [Hz] 0 [Hz]
p1272 Simulation mode / Simulation mode
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0