2 Parameters
2.2 List of parameters
SINAMICS G130/G150
970 List Manual (LH2), 04/2014, A5E03263479A
Index: [0] = Checksum HW-independent TM54F parameters
[1] = Checksum HW-dependent TM54F parameters (MM)
Description: Displays the reference checksum of the checksum-checked parameters for the Terminal Module 54F (TM54F).
Index: [0] = Checksum HW-independent TM54F parameters
[1] = Checksum HW-dependent TM54F parameters (MM)
Description: Select a fail-safe digital input for the signal "acknowledge internal event" (internal fault).
The signal is transferred to the corresponding control signal of all drives.
The falling edge at this input resets the status "internal event" in the drives.
The rising edge at this input acknowledges any existing discrepancy errors.
Value: 0: Statically active
1: F-DI 0 (X521.2/3/6)
2: F-DI 1 (X521.4/5/7)
3: F-DI 2 (X522.1/2/7)
4: F-DI 3 (X522.3/4/8)
5: F-DI 4 (X522.5/6/9)
6: F-DI 5 (X531.2/3/6)
7: F-DI 6 (X531.4/5/7)
8: F-DI 7 (X532.1/2/7)
9: F-DI 8 (X532.3/4/8)
10: F-DI 9 (X532.5/6/9)
255: Statically inact
Note: The values "static active" and "static inactive" result in an inactive function of the safe acknowledgment.
F-DI: Failsafe Digital Input
Description: Sets the signal source to initiate the test stop.
For example, a digital input of the Control Unit or one of the other Terminal Modules can be set as signal source.
The test stop is triggered on a 0/1 signal edge.
The TM54F must be in the "ready" state (p0010 = 0).
Dependency: Refer to: p10001, p10003, p10041, p10046
Notice: Digital inputs of the TM54F must not be used to trigger the test stop.
p10005[0...1] SI TM54F parameter target checksum / SI par CRC target
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: 2847
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0000 hex FFFF FFFF hex 0000 hex
p10006 SI TM54F acknowledgement internal event input terminal / SI ackn int event
TM54F_MA,
TM54F_SL
Can be changed: C2(95) Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 255 0
p10007 BI: SI TM54F forced checking procedure F-DI/F-DO signal source / SI dynF-DI/DOs_src
TM54F_MA Can be changed: C2(95) Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2848
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0