SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
103
2 Parameters
2.2 List of parameters
Note: For parallel circuit configurations, the parameter index is assigned to a power unit.
Description: Overloading the load duty cycles applies under the prerequisite that before and after the overload, the drive converter
is operated with its base load current - in this case, a load duty cycle of 300 s is used as basis.
For booksize drive units, the following applies:
Only the setting p0205 = 0 can be selected. In this particular case, the base load current has a load duty cycle of 150
% for 60 s and 176 % for 30 s.
For chassis units, the following applies:
The base load current for a low overload condition is based on a load duty cycle 110 % for 60 s and 150 % for 10 s.
The base load current for a high overload condition is based on a load duty cycle 150 % for 60 s and 160 % for 10 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
6: S1 duty cycle for servo drives (feed drive)
7: S6 duty cycle for servo drives (spindle drive)
Note: When the parameter is changed, all of the motor parameters and the control mode are pre-assigned according to the
selected application.
The parameter has no influence when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
Description: Displays the rated power unit power for various load duty cycles.
Index: [0] = Rated value
[1] = Load duty cycle with low overload
[2] = Load duty cycle with high overload
[3] = S1 cont duty cyc
[4] = S6 load duty cycle
Bit field: Bit Signal name 1 signal 0 signal FP
00 Device type DC/AC device AC/AC device -
01 RFI filter available Yes No -
02 Active Line Module available Yes No -
03 Smart Line Module available Yes No -
04 Basic Line Module available with thyristor
bridge
Yes No -
05 Basic Line Module available with diode
bridge
Yes No -
06 Liquid cooling with cooling unit (chassis PU) Yes No -
07 F3E regenerative feedback into the line
supply
Yes No -
08 Internal Braking Module Yes No -
09 Different cooling type supported Yes No -
12 Safe Brake Control (SBC) supported No Yes -
13 Safety Integrated supported Yes No -
14 Internal LC output filter Yes No -
15 Line voltage 1-phase 3-phase -
p0205 Power unit application / PU application
VECTOR_G Can be changed: C2(1, 2) Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 7 6
r0206[0...4] Rated power unit power / PU P_rated
B_INF, VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: 14_6 Unit selection: p0100
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- [kW] - [kW] - [kW]