2 Parameters
2.2 List of parameters
Description: Displays actual absolute current.
Index: [0] = Unsmoothed
[1] = Smoothed with p0045
Dependency: Refer to: r0027
Notice: The value is updated with the current controller sampling time.
Note: Absolute current value = sqrt(Iq^2 + Id^2)
The absolute value of the current actual value is available smoothed (r0027 with 300 ms, r0068[1] with p0045) and
unsmoothed (r0068[0]).
Description: Display and connector output for the measured actual phase currents as peak value.
Index: [0] = Phase U
[1] = Phase V
[2] = Phase W
[3] = Phase U offset
[4] = Phase V offset
[5] = Phase W offset
[6] = Total U, V, W
Note: In indices 3 ... 5, the offset currents of the 3 phases, which are added to correct the phase currents, are displayed.
The sum of the 3 corrected phase currents is displayed in index 6.
Description: Display and connector output for the measured actual value of the DC link voltage.
Dependency: Refer to: r0026
Note: The DC link voltage is available smoothed (r0026) and unsmoothed (r0070).
r0068[0...1] CO: Absolute current actual value / I_act abs val
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6300, 6714,
6799, 7017, 8014, 8017, 8018
P-Group: Displays, signals Units group: 6_2 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [Arms] - [Arms] - [Arms]
r0069[0...6] CO: Phase current actual value / I_phase act value
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6730, 6731,
6732, 7983, 7987, 8850, 8950
P-Group: Displays, signals Units group: 6_5 Unit selection: p0505
Not for motor type: - Scaling: p2002 Expert list: 1
Min Max Factory setting
- [A] - [A] - [A]
r0070 CO: Actual DC link voltage / Vdc act val
B_INF Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8750, 8850,
8910, 8940, 8950, 8964
P-Group: Displays, signals Units group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [V] - [V] - [V]