SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
309
2 Parameters
2.2 List of parameters
Description: Displays the acceleration of the ramp-function generator.
Dependency: Refer to: p1145
Description: Displays the setpoint at the output of the ramp-function generator.
Description: Sets the configuration for the extended ramp-function generator.
Dependency: Re bit 01, 02 = 1:
These bits are only effective when ramp-function generator tracking is activated (p1145 > 0).
When both bits are activated, RFG tracking with polarity change is active.
Re bit 01 = 0, bit 02 = 0:
When ramp-function generator tracking is active, the setpoint can only change in the direction of the target setpoint –
or be frozen.
Notice: Re bit 00 = 1:
If the ramp-up time is longer than the ramp-down time (p1120 > p1121), then there is an acceleration step at the zero
crossover. This can have a negative impact on the mechanical system.
Note: Re bit 00 = 1:
When the direction change is changed there is no rounding-off before and after the zero crossover.
Re bit 01 = 1:
For load surges, the ramp-function generator output tracks the actual value. The tracking (correction) ends at a
setpoint of zero.
Re bit 02 = 1:
For load surges, the ramp-function generator output tracks the actual value. For a polarity change, the tracking
(correction) is continued.
r1149 CO: Ramp-function generator acceleration / RFG acceleration
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3060, 3070
P-Group: Setpoints Units group: 39_1 Unit selection: p0505
Not for motor type: - Scaling: p2007 Expert list: 1
Min Max Factory setting
- [rev/s²] - [rev/s²] - [rev/s²]
r1150 CO: Ramp-function generator speed setpoint at the output / RFG n_set at outp
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3001, 3080
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]
p1151[0...n] Ramp-function generator configuration / RFG config
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned16 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Disable rounding-off at the zero cross-over Yes No 3070
01 RFG tracking without polarity change Yes No -
02 RFG tracking with polarity change Yes No -