2 Parameters
2.2 List of parameters
SINAMICS G130/G150
310 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal source for "setpoint 2 enable".
Description: Sets the signal source for speed setpoint 1 of the speed controller.
Dependency: The effectiveness of this setpoint depends on, e.g. STW1.4 and STW1.6.
Refer to: r0002, p0840, p0844, p0848, p0852, p0854, r0898, p1140, p1142, p1160, r1170, p1189
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for speed setpoint 2 of the speed controller.
Dependency: Refer to: p1155, r1170
Note: For OFF1/OFF3, the ramp-function generator ramp is effective.
The ramp-function generator is set (SERVO: to the actual value, VECTOR: To the setpoint (r1170)) and stops the
drive corresponding to the ramp-downtime (p1121 or p1135). While stopping via the ramp-function generator,
STW1.4 is effective (enable ramp-function generator).
When the function module "position control" (r0108.3 = 1) is activated, this connector input is interconnected as
follows as standard:
CI: p1160 = r2562
Description: Displays the speed setpoint after the addition of the speed setpoint 1 (p1155) and speed setpoint 2 (p1160).
Dependency: Refer to: p1155, p1160
Note: The value is only correctly displayed at r0899.2 = 1 (operation enabled).
p1152 BI: Setpoint 2 enable / Setp 2 enab
VECTOR_G (Ext
brake)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2711, 4015
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 899.15
p1155[0...n] CI: Speed controller speed setpoint 1 / n_ctrl n_set 1
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3080,
5030, 6031
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
p1160[0...n] CI: Speed controller speed setpoint 2 / n_ctrl n_set 2
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: CDS, p0170 Func. diagram: 3001, 3080
P-Group: Setpoints Units group: - Unit selection: -
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- - 0
r1169 CO: Speed controller speed setpoints 1 and 2 / n_ctrl n_set 1/2
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 3080
P-Group: Setpoints Units group: 3_1 Unit selection: p0505
Not for motor type: - Scaling: p2000 Expert list: 1
Min Max Factory setting
- [rpm] - [rpm] - [rpm]