SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
93
2 Parameters
2.2 List of parameters
Description: Sets the component number for the Terminal Module.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a Terminal Module.
Description: The VSM data set is assigned to a VSM evaluation using this parameter.
Note: If two VSM are connected at the Motor Module, then the first (p0151[0]) is assigned to the line voltage measurement
(see p3801) and the second, to the motor voltage measurement (see p1200).
Description: Detects any DRIVE-CLiQ Hub Module that has been assigned.
Description: Detects the Terminal Module assigned to this drive and data set.
Note: While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Terminal Module.
Description: Setting to activate/de-activate a Voltage Sensing Module (VSM).
Value: 0: De-activate component
1: Activate component
2: Component de-activate and not present
p0151 Terminal Module component number / TM comp_no
TM150, TM31,
TM54F_MA,
TM54F_SL
Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0151[0...n] Voltage Sensing Module component number / VSM comp_no
VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: p0150 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0154 DRIVE-CLiQ Hub Module detection via LED / Hub detection LED
HUB Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0154 Terminal Module detection via LED / TM detection LED
TM150, TM31,
TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0155[0...n] Voltage Sensing Module activate/de-activate / VSM act/deact
VECTOR_G Can be changed: C1(4), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: p0150 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1