EasyManua.ls Logo

Siemens SINAMICS G150 - Terminal Module Component Number; TM Comp_No; Voltage Sensing Module Component Number; VSM Comp_No; DRIVE-Cliq Hub Module Detection Via LED; Hub Detection LED; Terminal Module Detection Via LED; TM Detection LED

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
93
2 Parameters
2.2 List of parameters
Description: Sets the component number for the Terminal Module.
This unique component number is assigned when parameterizing the topology.
Only component numbers can be entered into this parameter that correspond to a Terminal Module.
Description: The VSM data set is assigned to a VSM evaluation using this parameter.
Note: If two VSM are connected at the Motor Module, then the first (p0151[0]) is assigned to the line voltage measurement
(see p3801) and the second, to the motor voltage measurement (see p1200).
Description: Detects any DRIVE-CLiQ Hub Module that has been assigned.
Description: Detects the Terminal Module assigned to this drive and data set.
Note: While p0154 = 1, the READY LED flashes green/orange or red/orange with 2 Hz at the appropriate Terminal Module.
Description: Setting to activate/de-activate a Voltage Sensing Module (VSM).
Value: 0: De-activate component
1: Activate component
2: Component de-activate and not present
p0151 Terminal Module component number / TM comp_no
TM150, TM31,
TM54F_MA,
TM54F_SL
Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0151[0...n] Voltage Sensing Module component number / VSM comp_no
VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: p0150 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 199 0
p0154 DRIVE-CLiQ Hub Module detection via LED / Hub detection LED
HUB Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0154 Terminal Module detection via LED / TM detection LED
TM150, TM31,
TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p0155[0...n] Voltage Sensing Module activate/de-activate / VSM act/deact
VECTOR_G Can be changed: C1(4), T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: p0150 Func. diagram: -
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1