2 Parameters
2.2 List of parameters
Caution: For p1999 > 100 % (setting large moments of inertia) the following applies:
There is no locked rotor monitoring (F07970 fault value 2).
The plausibility check of the encoder signal (F07970 fault value 4) only checks the sign.
Note: For high moments of inertia, it is practical to scale the runtime of the calibration higher.
Description: Sets the reference quantity for the frequency.
All frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz)
Description: Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
Description: Sets the reference quantity for velocity and frequency.
All velocities or frequencies specified as relative value are referred to this reference quantity.
The reference quantity corresponds to 100% or 4000 hex (word) or 4000 0000 hex (double word).
The following applies: Reference frequency (in Hz) = reference velocity (in (m/min) / 60)
Note: If a BICO interconnection is established between different physical quantities, then the particular reference quantities
are used as internal conversion factor.
Description: Sets the reference quantity for speed and frequency.
All speeds or frequencies specified as relative value are referred to this reference quantity.
p2000 Reference frequency / f_ref
B_INF Can be changed: T Calculated: CALC_MOD_ALL Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.10 [Hz] 1000.00 [Hz] 50.00 [Hz]
p2000 Reference speed reference frequency / n_ref f_ref
ENC Can be changed: T Calculated: CALC_MOD_ALL Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
6.00 [rpm] 210000.00 [rpm] 3000.00 [rpm]
p2000 Reference velocity reference frequency / v_ref f_ref
ENC (Lin_enc) Can be changed: T Calculated: CALC_MOD_ALL Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.60 [m/min] 600.00 [m/min] 120.00 [m/min]
p2000 Reference speed reference frequency / n_ref f_ref
VECTOR_G Can be changed: T Calculated: CALC_MOD_ALL Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Communications Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
6.00 [rpm] 210000.00 [rpm] 3000.00 [rpm]