EasyManua.ls Logo

Siemens SINAMICS G150 - Motor Temperature Sensor 4 Sensor Type; Temp_Sens 4 Type; Motor Temperature Sensor 1 Sensor Type MDS; Temp Sens1 Typ MDS; Motor Temperature Sensor 2 Sensor Type MDS; Temp Sens2 Typ MDS

Siemens SINAMICS G150
1842 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Parameters
2.2 List of parameters
SINAMICS G130/G150
638 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the sensor type of the fourth temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 10.
Terminals for PTC triplet: X200.5, X200.6
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Description: Sets the sensor type of the first temperature sensor for the motor temperature monitoring.
Value: 0: No sensor
10: PTC fault
11: PTC alarm
12: PTC alarm & timer
20: KTY84, PT100, PT1000
30: Bimetallic NC contact fault
31: Bimetallic NC contact alarm
32: Bimetallic NC contact alarm & timer
Dependency: Refer to: r0458, p0600, p0601
Note: This parameter is effective only when p0601 = 11.
PTC thermistor: Tripping resistance = 1650 Ohm
Information on using temperature sensors is provided in the following literature:
- hardware description of the appropriate components
- SINAMICS S120 Commissioning Manual
Description: Sets the sensor type of the second temperature sensor for the motor temperature monitoring.
p4603[0...n] Motor temperature sensor 4 sensor type / Temp_sens 4 type
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: EDS, p0140 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 0
p4610[0...n] Motor temperature sensor 1 sensor type MDS / Temp sens1 typ MDS
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 10
p4611[0...n] Motor temperature sensor 2 sensor type MDS / Temp sens2 typ MDS
VECTOR_G Can be changed: C2(3), U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: MDS, p0130 Func. diagram: 8016
P-Group: Motor Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 32 10

Table of Contents