2 Parameters
2.2 List of parameters
SINAMICS G130/G150
1000 List Manual (LH2), 04/2014, A5E03263479A
Value: 0: Brake test inactive, wait for SBT selection
1: Setpoint input drive
2: Determining the load
3: Brake test is initialized, wait for start of test sequence
4: Start test seq
5: Closing the brake, establishing the test torque
6: Brake test active, wait for test duration sequence
7: Reduce test torque
8: Wait for the brake to open
9: Brake test successfully completed, wait for start deselection
10: Change to brake test initialized - fault acknowledgment
11: Brake test canceled, torque is reduced
12: Brake test canceled, wait for brake to open
13: Brake test ended with error, wait for acknowledgment
14: Brake opening timer elapsed
15: Error when initializing the brake test, wait for acknowledgment
16: Change to brake test inactive, acknowledgment active
Description: Sets the signal source for control word S_STW1B of the Safety Control Channel.
Dependency: Refer to: p10203, r10251
Note: SCC: Safety Control Channel
Description: Display and BICO output for the diagnostics of control word S_STW1B of the safety control channel.
Dependency: Refer to: p10250
Note: SCC: Safety Control Channel
Description: Sets the telegram number for PROFIsafe.
p10250 CI: SI Safety Control Channel control word S_STW1B / SCC S_STW1B
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r10251.8...12 CO/BO: SI Safety Control Channel control word S_STW1B diagnostics /
SCC S_STW1B diag
VECTOR_G Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
08 Extended functions test stop selection Selected Not selected 2837
09 Extended Functions referencing trigger Selected Not selected -
10 Extended Functions referencing reset Selected Not selected -
12 Extended Functions premature SOS after
STOP D
Selected Not selected -
p60022 PROFIsafe telegram selection / Ps telegram_sel
VECTOR_G Can be changed: T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Safety Integrated Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 902 0