2 Parameters
2.2 List of parameters
Description: Sets a dynamic voltage reserve.
Note: In the field weakening range, it must be expected that the control dynamic performance is somewhat restricted due to
the limited possibilities of controlling/adjusting the voltage. This can be improved by increasing the voltage reserve.
Increasing the reserve reduces the steady-state maximum output voltage (r0071).
Description: Sets the limit of the voltage target value.
In steady-state field weakening operation this corresponds to the required output voltage.
The value of 100% refers to p0304.
Note: The output voltage is only limited if the maximum output voltage (r0071) minus the voltage reserve (p1574)
corresponds to a value higher than p1575.
Limiting via p1575 allows the influence of the voltage ripple of the line supply voltage to be eliminated at the operating
point.
Description: Sets the lower adaptation speed of the flux boost.
Below this speed, p1570 is set as reference (setpoint) flux.
Description: Sets the upper adaptation speed of the flux boost.
Above this speed, the rated motor flux (100 %) is set as reference (setpoint) flux.
Dependency: The parameter value refers to the lower adaptation speed of the flux boost.
Refer to: p1576
p1574[0...n] Voltage reserve dynamic / U_reserve dyn
VECTOR_G (n/M) Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6723, 6724
P-Group: Closed-loop control Units group: 5_1 Unit selection: p0505
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [Vrms] 150.0 [Vrms] 10.0 [Vrms]
p1575[0...n] Voltage target value limit / U_tgt val lim
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6725
P-Group: - Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
50.00 [%] 200.00 [%] 200.00 [%]
p1576[0...n] Flux boost adaptation speed, lower / Flux boost n lower
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6725
P-Group: Closed-loop control Units group: 3_1 Unit selection: p0505
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.00 [rpm] 210000.00 [rpm] 0.00 [rpm]
p1577[0...n] Flux boost adaptation speed upper / Flux boost n upper
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_ALL Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6725
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
1.0 [%] 10000.0 [%] 200.0 [%]