2 Parameters
2.2 List of parameters
SINAMICS G130/G150
580 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the threshold value of the phase synchronism for the line-drive synchronization.
A prerequisite for synchronism is achieved if the phase difference is lower than the threshold value.
Note: Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
Description: Display and connector output for the voltage difference between the measured target voltage and output voltage of
the gating unit of the closed-loop control for line-drive synchronization.
Description: Sets the threshold value of the voltage difference for the line-drive synchronization.
A prerequisite for synchronism is reached if the voltage difference is less than the threshold value.
Note: Synchronism is reached (r3819.2 = 1), if the AND logic operation of the results from the phase measurement (p3813)
and voltage measurement (p3815) is fulfilled.
For voltage manipulated quantity margin (reserve) of the drive converter, the amplitude difference (r3814) between
the setpoint and actual value is controlled (corrected) to zero.
Description: Displays the status word for the line-drive synchronization.
p3813[0...n] Sync-line-drive phase synchronism threshold value / Sync Ph_sync thrsh
VECTOR_G Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1.00 [°] 20.00 [°] 2.00 [°]
r3814 CO: Sync-line-drive voltage difference / Sync U_diff
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- [Vrms] - [Vrms] - [Vrms]
p3815[0...n] Sync-line-drive voltage difference threshold value / Sync U_diff thresh
VECTOR_G Can be changed: U, T Calculated:
CALC_MOD_LIM_REF
Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.00 [%] 20.00 [%] 10.00 [%]
r3819.0...7 CO/BO: Sync-line-drive status word / Sync ZSW
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 7020
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Sync-line-drive enabled Yes No -
02 Sync-line-drive synchronism reached Yes No -
03 Sync-line-drive synchronizing error Yes No -
05 Sync-line-drive frequency measurement
active
Yes No -
06 Sync-line-drive phase control active Yes No -
07 Sync-line-drive without drive Yes No -