SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
727
2 Parameters
2.2 List of parameters
Description: Displays the parameter value read from the DRIVE-CLiQ component.
Dependency: Refer to: p7820, p7821, p7822
Description: Displays the firmware and EEPROM versions of the DRIVE-CLiQ component selected using p7828[1].
Index: [0] = Reference firmware version
[1] = Actual firmware version
[2] = EEPROM0 version
[3] = EEPROM1 version
[4] = EEPROM2 version
[5] = EEPROM3 version
[6] = EEPROM4 version
Dependency: Refer to: p7828
Note: Re index 0:
Firmware version on the memory card/device memory.
Re index 1:
Actual firmware version of the DRIVE-CLiQ component.
Re index 2 ... 6:
Actual EEPROM version of the DRIVE-CLiQ component.
Description: Sets the behavior for the automatic firmware update of the DRIVE-CLiQ components.
Value: 0: Deactivated
1: Upgrade and downgrade
2: Upgrade
Notice: If this parameter is changed, it only becomes effective the next time that the drive system boots.
Note: The firmware is automatically updated when the system boots. The boot can take several minutes.
After the update has been completed, it is necessary to carry out a new POWER ON (power-down/power-up) for the
components involved.
The firmware update procedure is displayed as follows:
Control Unit (LED RDY):
Flashes yellow with 0.5 Hz --> firmware is being updated.
Flashing yellow with 2 Hz --> POWER ON is required for the components involved.
r7823 DRIVE-CLiQ component read parameter value / Read DQ value
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r7825[0...6] DRIVE-CLiQ component versions / DQ comp version
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
p7826 Firmware update automatic / FW update auto
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 2 1