2 Parameters
2.2 List of parameters
SINAMICS G130/G150
154 List Manual (LH2), 04/2014, A5E03263479A
Re bit 12 (equidistant zero mark):
The zero marks occur at regular intervals (e.g. rotary encoder with 1 zero mark per revolution or linear encoder with
constant zero mark distance).
The bit activates monitoring of the zero mark distance (p0424/p0425, linear/rotary) or in the case of the linear
encoder with 1 zero mark and p0424 = 0 zero mark monitoring is activated.
Re bit 13 (irregular zero mark):
The zero marks occur at irregular intervals (e.g. a linear scale with only 1 zero mark in the traversing range). The zero
mark distance is not monitored.
Re bit 14 (distance-coded zero mark):
The distance (clearance) between two or several consecutive zero marks allows the absolute position to be
calculated.
Re bit 15 (commutation with zero mark):
Only applicable for synchronous motors.
The function can be de-selected by priority via p0430.23.
For distance-coded zero marks, the following applies:
The phase sequence of the C/D track (if available) must be the same as the phase sequence of the encoder (A/B
track).
The phase sequence of the Hall signal (if available) must be the same as the phase sequence of the motor. Further,
the position of the Hall sensor must be mechanically adjusted to the motor EMF.
The fine synchronization is only started after two zero marks have been passed.
Description: Settings for the track A/B in a square-wave encoder.
For square-wave encoders, p0404.3 must also be 1.
Notice: This parameter is automatically pre-set for encoders from the encoder list (p0400).
When selecting a catalog encoder, this parameter cannot be changed (write protection). Information in p0400 should
be carefully observed when removing write protection.
Note: Re bit 02:
When the function is activated, track monitoring can be de-activated by setting p0437.26.
Re bit 05:
When the function is activated, a frequency setpoint and a direction for traveling can be entered via an encoder
interface.
Description: Sets the grid division for a linear encoder.
p0405[0...n] Square-wave encoder track A/B / Sq-wave enc A/B
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 1111 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 Signal Bipolar Unipolar -
01 Level TTL HTL -
02 Track monitoring A/B <> -A/B None -
03 Zero pulse Same as A/B track 24 V unipolar -
04 Switching threshold High Low -
05 Pulse/direction Active Inactive -
p0407[0...n] Linear encoder grid division / Enc grid div
ENC, VECTOR_G Can be changed: C2(4) Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: EDS, p0140 Func. diagram: 4010, 4704
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [nm] 250000000 [nm] 16000 [nm]