2 Parameters
2.2 List of parameters
Description: Displays the error code of the invalid OA applications installed on the memory card/device memory.
r4979[0]: Fault value of OA application 1
r4979[1]: Fault value of OA application 2, ...
Dependency: Refer to: r4975, r4976, r4978
Notice: If there is no invalid OA application, then it is not possible to access an index.
Note: The value in the error code must be interpreted in binary form. The bits have the following meaning:
Bit 0: Incompatible OA interface version.
Bit 1: OA application could not be loaded.
Bit 2: Incorrect description files.
Bit 3: OA application does not define a CPU type.
Bit 4: OA application for this device not supported (incorrect CPU type).
Bit 5: OA application for this device not supported (incorrect type ID).
Bit 6: Incorrect description files (Const/Startup incompatible).
Description: Displays the number of OA applications installed on the memory card/device memory.
Dependency: Refer to: r4986, r4987, r4988, r4989, r4990, r4991, r4992, r4993, r4994
Note: OA: Open Architecture (OA application)
Description: Displays the total length of the IDs of all the OA applications installed on the memory card/device memory.
Dependency: Refer to: r4985, r4987, r4988, r4989, r4990, r4991, r4992, r4993, r4994
Note: The identifier of an OA application comprises a maximum of 8 characters plus separator.
Description: Displays the total length of the GUIDs of all the OA applications installed on the memory card/device memory.
Dependency: Refer to: r4985, r4986, r4988, r4989, r4990, r4991, r4992, r4993, r4994
r4979[0...n] OA invalid error code / OA inv error code
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned32 Dyn. index: r4975 Func. diagram: -
P-Group: OEM range Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r4985 OA number / OA no
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: OEM range Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 16 -
r4986 OA identifier total length / OA id tot_length
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: OEM range Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 144 -
r4987 OA GUID total length / OA GUID tot_length
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 4
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: OEM range Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 288 -