2 Parameters
2.2 List of parameters
SINAMICS G130/G150
96 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the number of Command Data Sets (CDS).
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
Description: Sets the number of Command Data Sets (CDS).
Note: It is possible to toggle between command parameters (BICO parameters) using this data set changeover.
Description: Sets the number of Drive Data Sets (DDS).
Description: Using the parameter, each Drive Data Set (= index) is assigned the associated Motor Data Set (MDS).
The parameter value therefore corresponds to the number of the assigned motor data set.
Description: Assign a drive data set (= index) the corresponding encoder data set (EDS) for encoder 1.
The value corresponds to the number of the assigned encoder data set.
Example:
Encoder data set 0 should be assigned to encoder 1 in drive data set 2.
--> p0187[2] = 0
p0170 Number of Command Data Sets (CDS) / CDS count
B_INF Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 2 1
p0170 Number of Command Data Sets (CDS) / CDS count
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
2 4 2
p0180 Number of Drive Data Sets (DDS) / DDS count
VECTOR_G Can be changed: C1(3) Calculated: - Access level: 2
Data type: Unsigned8 Dyn. index: - Func. diagram: 8565
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
1 32 1
p0186[0...n] Motor Data Sets (MDS) number / MDS number
VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: DDS, p0180 Func. diagram: 8575
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 15 0
p0187[0...n] Encoder 1 encoder data set number / Enc 1 EDS number
VECTOR_G Can be changed: C1(4) Calculated: - Access level: 3
Data type: Unsigned8 Dyn. index: DDS, p0180 Func. diagram: 4700, 8570
P-Group: Data sets Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 99 99