2 Parameters
2.2 List of parameters
SINAMICS G130/G150
568 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the total DC link capacitance for closed-loop voltage control.
The capacitance of one power unit is pre-assigned to this value. The value should be adapted according to the
number of power units.
Note: The controller setting for the DC-link voltage controller is derived from this value.
Description: Sets the delay time for the ON/OFF1 command of the infeed.
After ON/OFF1 = 0 the infeed remains in operation for the specified time
Dependency: Refer to: p0840
Notice: The ON/OFF1 command of the infeed can be interrupted.
Note: This parameter is only relevant if a Motor Module and the infeed are controlled by the same OFF command. In this
case, the delay time and the stop ramp time of the motor can be coordinated with one another.
Description: Sets the setpoint for the DC-link voltage on the motor side.
Description: Sets the signal source for the supplementary setpoint for the DC-link voltage on the motor side.
Dependency: Refer to: p3510
p3422 DC link capacitance total / C_DC tot
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.20 [mF] 2000.00 [mF] 2.00 [mF]
p3490 Infeed delay time OFF1 command / INF t_del OFF1
B_INF Can be changed: T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 8732, 8832,
8932
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.0 [ms] 1000000.0 [ms] 0.0 [ms]
p3510 DC link voltage setpoint / Vdc setp
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: 5_2 Unit selection: p0505
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
100.00 [V] 1600.00 [V] 600.00 [V]
p3511 CI: DC link voltage supplementary setpoint / Vdc Z_set
VECTOR_G
(Tech_ctrl)
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / FloatingPoint32 Dyn. index: - Func. diagram: 7960
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: - Scaling: p2001 Expert list: 1
Min Max Factory setting
- - 0