2 Parameters
2.2 List of parameters
Index: [0] = AO 0 (X522.1, X522.2, X522.3)
[1] = AO 1 (X522.4, X522.5, X522.6)
Dependency: The unit of this parameter (V or mA) depends on the analog input type.
Refer to: r4076, p4076
Note: This means, for example, the offset of a downstream isolating amplifier can be compensated.
Description: Sets the simulation mode for the digital inputs of the Terminal Board 30 (TB30).
Dependency: The setpoint for the input signals is specified using p4096.
Refer to: p4096
Warning: A drive that is moved by simulating the inputs of a Terminal Board is brought to a standstill while the Terminal Module
is being activated or de-activated.
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
Description: Sets the simulation mode for the digital inputs of Terminal Module 31 (TM31).
Dependency: The setpoint for the input signals is specified using p4096.
Refer to: p4096
Warning: A drive that is moved by simulating the inputs of a Terminal Module is brought to a standstill while the Terminal
Module is being activated or de-activated.
Note: This parameter is not saved when data is backed-up (p0971, p0977).
DI: Digital Input
DI/DO: Bidirectional Digital Input/Output
p4095 TB30 digital inputs simulation mode / TB30 DI sim_mode
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9099, 9100
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X481.1) Simulation Terminal eval -
01 DI 1 (X481.2) Simulation Terminal eval -
02 DI 2 (X481.3) Simulation Terminal eval -
03 DI 3 (X481.4) Simulation Terminal eval -
p4095 TM31 digital inputs simulation mode / TM31 DI sim_mode
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 9549, 9550,
9552, 9560, 9562
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0000 0000 0000 0000 bin
Bit field: Bit Signal name 1 signal 0 signal FP
00 DI 0 (X520.1) Simulation Terminal eval -
01 DI 1 (X520.2) Simulation Terminal eval -
02 DI 2 (X520.3) Simulation Terminal eval -
03 DI 3 (X520.4) Simulation Terminal eval -
04 DI 4 (X530.1) Simulation Terminal eval -
05 DI 5 (X530.2) Simulation Terminal eval -
06 DI 6 (X530.3) Simulation Terminal eval -
07 DI 7 (X530.4) Simulation Terminal eval -
08 DI/DO 8 (X541.2) Simulation Terminal eval -
09 DI/DO 9 (X541.3) Simulation Terminal eval -
10 DI/DO 10 (X541.4) Simulation Terminal eval -
11 DI/DO 11 (X541.5) Simulation Terminal eval -