2 Parameters
2.2 List of parameters
SINAMICS G130/G150
554 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the tolerance window for time synchronization.
When this tolerance window is exceeded, an appropriate alarm is output.
Description: Sets the delay time for external fault 3.
Dependency: Refer to: p2108, p3111, p3112
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
Description: Sets the signal source for the enable signal of external fault 3.
External fault 3 is initiated by the following AND logic operation:
- BI: p2108 negated
- BI: p3111
- BI: p3112 negated
Dependency: Refer to: p2108, p3110, p3112
p3109 RTC real time synchronization tolerance window / RTC sync tol
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 100 [ms]
p3110 External fault 3 power-up delay / Ext fault 3 t_on
All objects Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 1000 [ms] 0 [ms]
p3111[0...n] BI: External fault 3 enable / Ext fault 3 enab
B_INF, VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: CDS, p0170 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1
p3111 BI: External fault 3 enable / Ext fault 3 enab
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN, ENC,
HUB, TB30, TM150,
TM31, TM54F_MA,
TM54F_SL
Can be changed: U, T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2546
P-Group: Messages Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 1