2 Parameters
2.2 List of parameters
SINAMICS G130/G150
660 List Manual (LH2), 04/2014, A5E03263479A
Index: [0] = Trace 0
[1] = Trace 1
Dependency: Only valid when p4705 = 4.
Description: Sets the recording cycle for the trace.
Index: [0] = Trace 0
[1] = Trace 1
Description: Sets the recording time for the trace.
Index: [0] = Trace 0
[1] = Trace 1
Description: Sets the trigger delay for the trace.
Trigger delay < 0:
Pretrigger: Tracing (recording) starts the selected time before the trigger event actually occurs.
Trigger delay > 0:
Post trigger: Tracing does not start until the set time after the trigger event.
Index: [0] = Trace 0
[1] = Trace 1
Description: Sets the time slice cycle in which the trace is called.
Index: [0] = Trace 0
[1] = Trace 1
p4720[0...1] Trace recording cycle / Trace record_cyc
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.000 [ms] 60000.000 [ms] 1.000 [ms]
p4721[0...1] Trace recording time / Trace record_time
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.000 [ms] 3600000.000 [ms] 1000.000 [ms]
p4722[0...1] Trace trigger delay / Trace trig_delay
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
-3600000.000 [ms] 3600000.000 [ms] 0.000 [ms]
p4723[0...1] Trace time slice cycle / Trace cycle
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Trace and function generator Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 0
Min Max Factory setting
0.03125 [ms] 4.00000 [ms] 0.12500 [ms]