Fig. 3-68 2548 – Status word, faults/alarms 1 and 2
- 2548 -
Function diagram
87654321
fp_2548_51_eng.vsd
DO: All objects
SINAMICS
18.02.14 V04.07.00
Internal control/status words - Status word, faults/alarms 1 and 2
Source sampling time
3
...
9
r2135
ZSW faults/alarms 2
0
r2139.3
r2139.7
r2135.14
r2135.15
r2135.13
r2135.12
r2139.0
r2139.6
r2135.0
r2135.1
r2135.2
From the thermal monitoring, power unit [8014.8]
From the thermal monitoring, power unit [8014.8]
From the thermal monitoring, motor [8016.8]
From the thermal monitoring, motor [8016.8]
r2139.8
From the alarm buffer [8065.4]
From the fault buffer [8060.7]
1 = Fault encoder 1
Status word, faults/alarms 2
1 = Fault encoder 2
1 = Fault encoder 3
1 = Alarm transformer overtemperature
1 = Fault motor overtemperature
1 = Fault power unit thermal overload
1 = Acknowledgement running
Status word, faults/alarms 1
1 = Fault present
Reserved
1 = Internal message 2 present
1 = Alarm motor overtemperature
1 = Alarm power unit thermal overload
1 = Internal message 1 present
1 = Alarm present
1 = Safety message present
2
1
Bit No.
r2139.5
4
6
7
8
12
13
14
15
0
Bit No.
5
3
r2139.11
Reserved9
Reserved10
1 = Alarm class bit 011
r2139.121 = Alarm class bit 112
1 = Acknowledgement required
Reserved
1
2
1 = Maintenance required13
1 = Maintenance urgently required14
1 = Fault gone/can be acknowledged15
11
1 = Fault transformer overtemperature10
<1> From the thermal monitoring, infeed
[8770.6]
[8970.6]
r2135.11
r2135.10
Reserved
<1>
<1>
<1>
<1>
<1> Only for A_INFMV, B_INFMV, VECTORMV, VECTORSL.
r2139
ZSW faults/alarms 1
r2139.1
r2139.13
r2139.14
r2139.15
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the alarm buffer [8065.4]
From the fault buffer [8060.7]