2 Parameters
2.2 List of parameters
SINAMICS G130/G150
234 List Manual (LH2), 04/2014, A5E03263479A
Permissible combinations in p0922 are:
p0922 = 391, 392, 393, 394
Re p0684 = 16:
Changing this evaluation procedure to p0684 = 0 or to p0684 = 1 is only activated after parameter save and POWER
ON.
Permissible combinations in p0922 are:
p0922 = 395
Description: Displays the control word for the function "central measuring probe evaluation".
Description: Displays the measuring time for a rising edge at the digital input for the "central measuring probe evaluation" function.
The measuring time is specified as 16-bit value with a resolution of 0.25 µs.
r0686[0]: Measuring time, rising edge measuring probe 1
r0686[1]: Measuring time, rising edge measuring probe 2
r0686[2]: Measuring time, rising edge measuring probe 3
r0686[3]: Measuring time, rising edge measuring probe 4
r0686[4]: Measuring time, rising edge measuring probe 5
r0686[5]: Measuring time, rising edge measuring probe 6
r0686[6]: Measuring time, rising edge measuring probe 7
r0686[7]: Measuring time, rising edge measuring probe 8
Note: The parameter is only active for the evaluation procedure p0684 = 0, 1.
For p0684 = 16, r0686[0...7] = 0 is displayed.
r0685 Central measuring probe control word display / Cen meas STW disp
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Falling edge measuring probe 1 Yes No -
01 Falling edge measuring probe 2 Yes No -
02 Falling edge measuring probe 3 Yes No -
03 Falling edge measuring probe 4 Yes No -
04 Falling edge measuring probe 5 Yes No -
05 Falling edge measuring probe 6 Yes No -
06 Falling edge measuring probe 7 Yes No -
07 Falling edge measuring probe 8 Yes No -
08 Rising edge measuring probe 1 Yes No -
09 Rising edge measuring probe 2 Yes No -
10 Rising edge measuring probe 3 Yes No -
11 Rising edge measuring probe 4 Yes No -
12 Rising edge measuring probe 5 Yes No -
13 Rising edge measuring probe 6 Yes No -
14 Rising edge measuring probe 7 Yes No -
15 Rising edge measuring probe 8 Yes No -
r0686[0...7] CO: Central measuring probe measuring time rising edge / CenMeas t_meas 0/1
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: - Calculated: - Access level: 3
Data type: Unsigned16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -