2 Parameters
2.2 List of parameters
SINAMICS G130/G150
576 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the activation threshold for the braking chopper.
Note: The activation threshold is only effective if the "Device supply voltage reduced" function (p0212.0 = 1) has been
activated!
Description: The binector output uses a 1 signal to indicate that 80 % of the highest permissible I2t value has been reached in the
Braking Module.
Description: The binector output uses a 1 signal to indicate an overcurrent fault or an I2t shutdown in the Braking Module.
Description: Displays a fault due to the excessively high temperature.
1 signal:
The connected temperature sensor (X21.1, X21.2) signals an overtemperature.
Recommend.: Measure the braking resistor temperature using the temperature sensor.
Description: Displays the shutdown due to the excessively high temperature.
p3683 Braking Module internal activation threshold brake chopper / BM int act thresh
B_INF Can be changed: C2(1) Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: Converter Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
110.00 [V] 780.00 [V] 760.00 [V]
r3685 BO: Digital Braking Module: Pre-alarm I2t shutdown / Dig BM A I2t shutd
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3686 BO: Digital Braking Module Fault / Dig BM Fault
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3687 BO: Digital Braking Module pre-alarm overtemperature / Dig BM A overtemp
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
r3688 BO: Braking Module internal overtemperature shutdown / BM int temp shutd
B_INF Can be changed: - Calculated: - Access level: 3
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -