SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
605
2 Parameters
2.2 List of parameters
Note: Prerequisite: The DI/DO must be set as an output (p4028.11 = 1).
DI/DO: Bidirectional Digital Input/Output
Description: Sets the limit for the total output voltage of terminals X541.1, X541.2, X541.3 and X541.4 (DI/DO 8 ... 11) of Terminal
Module 31 (TM31).
Value: 0: 0.1 A total current limit DI/DO 8 ... 11
1: 1.0 A total current limit DI/DO 8 ... 11
Dependency: Refer to: p4028
Warning: Since the sum of the output currents at terminals X541.1, X541.2, X541.3 and X541.4 is limited, an overcurrent or
short circuit at one output terminal can cause a dip in the signal at the other terminals.
Description: Displays the status of the digital outputs of the Terminal Board 30 (TB30).
Note: Inversion using p4048 has been taken into account.
DO: Digital Output
Description: Displays the status of the digital outputs of Terminal Module 31 (TM31).
Note: Inversion using p4048 has been taken into account.
The setting of the DI/DO as either input or output is of no significance (p4028).
DO: Digital Output
DI/DO: Bidirectional Digital Input/Output
p4046 TM31 digital outputs limit current / TM31 DO limit curr
TM31 Can be changed: T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9560
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
r4047 TB30 digital outputs status / TB30 DO status
TB30 Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9102
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X481.5) High Low -
01 DO 1 (X481.6) High Low -
02 DO 2 (X481.7) High Low -
03 DO 3 (X481.8) High Low -
r4047 TM31 digital outputs status / TM31 DO status
TM31 Can be changed: - Calculated: - Access level: 1
Data type: Unsigned32 Dyn. index: - Func. diagram: 9556, 9560,
9562
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (X542.1 - 3) High Low -
01 DO 1 (X542.4 - 6) High Low -
08 DI/DO 8 (X541.2) High Low -
09 DI/DO 9 (X541.3) High Low -
10 DI/DO 10 (X541.4) High Low -
11 DI/DO 11 (X541.5) High Low -