2 Parameters
2.2 List of parameters
SINAMICS G130/G150
338 List Manual (LH2), 04/2014, A5E03263479A
The "bypass" function can only be switched off again (p1260 = 0) if the bypass is not active or the bypass function
has a fault.
The corresponding function should be activated in p3800 for bypass with synchronization.
Description: Control and feedback signals of the bypass switch.
Dependency: Refer to: p2369
Note: Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder cables
should be controlled. These should be selected/dimensioned for switching under load.
Description: Sets the dead time for non-synchronized bypass.
Note: This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-
magnetizing time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
Description: Sets the delay time to switch back to converter operation for a non-synchronized bypass.
r1261.0...11 CO/BO: Bypass control/status word / Bypass STW / ZSW
VECTOR_G
(Tech_ctrl)
Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 Command switch motor - power unit Close Open -
01 Command switch motor - line supply Close Open -
02 Synchronization requested Yes No -
03 Staging status Active Not active -
05 Feedback signal switch motor - power unit Closed Opened -
06 Feedback signal switch motor - line supply Closed Opened -
07 Bypass command (from p1266) Yes No -
08 Feedback signal synchronization completed
(from p1268)
Yes No -
09 Staging requested (from p2369) Yes No -
10 Bypass in process sequence Yes No -
11 Bypass enabled Yes No -
p1262[0...n] Bypass dead time / Bypass t_dead
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: CALC_MOD_REG Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 20.000 [s] 1.000 [s]
p1263 Debypass delay time / Debypass t_del
VECTOR_G
(Tech_ctrl)
Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: -
P-Group: - Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0.000 [s] 300.000 [s] 1.000 [s]