2 Parameters
2.2 List of parameters
SINAMICS G130/G150
392 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the efficiency optimization.
When optimizing the efficiency, the flux setpoint of the closed-loop control is adapted as a function of the load.
For p1580 = 100 %, under no-load operating conditions, the flux setpoint is reduced to 50 % of the rated motor flux.
Note: It only makes sense to activate this function if the dynamic response requirements of the speed controller are low.
In order to avoid oscillations, if required, the speed controller parameters should be adapted (increase Tn, reduce
Kp).
Further, the smoothing time of the flux setpoint filter (p1582) should be increased.
Description: Sets the smoothing time for the flux setpoint.
Description: Displays the smoothed flux setpoint.
The value is referred to the rated motor flux.
Description: Sets the smoothing time for the flux setpoint in the field-weakening range
Recommend.: Smoothing should be especially used if there is no regenerative feedback into the line supply. This means that the
DC link voltage can quickly increase in regenerative operation
Note: Only the flux setpoint rise is smoothed
p1580[0...n] Efficiency optimization / Efficiency opt.
VECTOR_G (n/M) Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6722
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL, FEM Scaling: - Expert list: 1
Min Max Factory setting
0 [%] 100 [%] 0 [%]
p1582[0...n] Flux setpoint smoothing time / Flux setp T_smth
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6722, 6724,
6725
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: - Expert list: 1
Min Max Factory setting
4 [ms] 5000 [ms] 15 [ms]
r1583 Flux setpoint smoothed / Flux setp smooth
VECTOR_G (n/M) Can be changed: - Calculated: - Access level: 4
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 6722, 6723,
6724
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: REL Scaling: PERCENT Expert list: 1
Min Max Factory setting
- [%] - [%] - [%]
p1584[0...n] Field weakening operation flux setpoint smoothing time / Field weak T_smth
VECTOR_G (n/M) Can be changed: U, T Calculated: CALC_MOD_REG Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 6722
P-Group: Closed-loop control Units group: - Unit selection: -
Not for motor type: PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0 [ms] 20000 [ms] 0 [ms]