SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
233
2 Parameters
2.2 List of parameters
Notice: To the terminal designation:
The first designation is valid for CU320, the second for CU310.
To select the values:
For CX32, NX10 and NX15, only DI/DO 8, 9, 10, 11 can be selected as fast inputs (refer to the Equipment Manual).
Note: DI/DO: Bidirectional Digital Input/Output
Prerequisite: The DI/DO must be set as input (p0728.x = 0).
If a parameter change is rejected, a check should be performed as to whether the input terminal is already being
used in p0488, p0489, p0493, p0494, p0495, p0580, p2517 or p2518.
Description: Sets the signal source for the synchronizing signal (SYN) of the function "central measuring probe evaluation".
The signal is used to synchronize the common system time between the master and slave.
Notice: The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
Description: Sets the signal source for the control word of the function "central measuring probe evaluation".
Description: Sets the evaluation technique for the "central measuring probe evaluation" function.
Value: 0: Measurement with handshake
1: Measurement without handshake 2 edges
16: Measurement without handshake more than 2 edges
Notice: Re p0684 = 16:
This evaluation procedure is only activated after parameter save and POWER ON.
Note: During measurement without a handshake, the probe may have a higher evaluation frequency.
The setting "Measurement without handshake" must be supported by the higher-level control. This setting cannot be
used for SIMOTION D with integrated SINAMICS or with CX32.
Re p0684 = 0:
Changing this evaluation procedure to p0684 = 1 is possible in the RUN state.
Changing this evaluation procedure to p0684 = 16 is only activated after parameter save and POWER ON.
Permissible combinations in p0922 are:
p0922 = 391, 392, 393, 394
Re p0684 = 1:
Changing this evaluation procedure to p0684 = 0 is possible in the RUN state.
Changing this evaluation procedure to p0684 = 16 is only activated after parameter save and POWER ON.
p0681 BI: Central measuring probe synchronizing signal signal source / Cen meas sync_sig
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: -
P-Group: Commands Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0682 CI: Central measuring probe control word signal source / Cen meas STW S_src
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: T Calculated: - Access level: 3
Data type: Unsigned32 / Integer16 Dyn. index: - Func. diagram: -
P-Group: Displays, signals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
p0684 Central measuring probe evaluation technique / Cen meas eval_tech
CU_G130_DP,
CU_G130_PN,
CU_G150_DP,
CU_G150_PN
Can be changed: U, T Calculated: - Access level: 3
Data type: Integer16 Dyn. index: - Func. diagram: -
P-Group: Encoder Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 16 0