SINAMICS G130/G150
List Manual (LH2), 04/2014, A5E03263479A
561
2 Parameters
2.2 List of parameters
Description: Sets the hysteresis for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency: Refer to: p3201, p3203
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
Description: Sets the delay time for the "excitation current outside tolerance" message for the excitation current monitoring.
Dependency: Refer to: p3201, p3202
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
Description: Sets the threshold value for the "flux outside the tolerance" message for the flux monitoring.
If the absolute value of the difference between the flux setpoint and actual value (r0083 - r0084) falls below the
threshold value with hysteresis longer than the selected delay time, then fault F07914 is output.
This fault is withdrawn when the threshold voltage is undershot.
Dependency: Refer to: r0083, r0084, p3205, p3206
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
Description: Sets the hysteresis for the "flux outside tolerance" message for the flux monitoring.
Dependency: Refer to: p3204, p3206
Note: The monitoring function is only carried out for separately-excited synchronized motors (p0300 = 5).
The flux monitoring is only active after magnetizing (r0056.4 = 1).
p3202[0...n] Excitation current outside the tolerance hysteresis / I_exc n Tol hyst
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 100.0 [%] 10.0 [%]
p3203[0...n] Excitation current outside the tolerance delay time / I_exc n Tol t_del
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.0 [s] 10.0 [s] 1.0 [s]
p3204[0...n] Flux outside the tolerance threshold value / Flux n tol thresh
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 100.0 [%] 10.0 [%]
p3205[0...n] Flux outside the tolerance hysteresis / Flux n tol hyst
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: -
P-Group: Messages Units group: - Unit selection: -
Not for motor type: ASM, PEM, REL Scaling: - Expert list: 1
Min Max Factory setting
0.1 [%] 50.0 [%] 10.0 [%]