2 Parameters
2.2 List of parameters
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency: The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the simulation mode for the analog inputs of Terminal Module 31 (TM31).
Value: 0: Terminal evaluation for analog input x
1: Simulation for analog input x
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
Dependency: The setpoint for the input voltage is specified via p4098.
Refer to: p4098
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the setpoint for the input voltage in the simulation mode of the analog inputs of Terminal Board 30 (TB30).
Index: [0] = AI 0 (X482.1/X482.2)
[1] = AI 1 (X482.3/X482.4)
Dependency: The simulation of an analog input is selected using p4097.
Refer to: p4097
Note: This parameter is not saved when data is backed-up (p0971, p0977).
AI: Analog Input
Description: Sets the setpoint for the input value in simulation mode of the analog inputs of Terminal Module 31 (TM31).
Index: [0] = AI 0 (X521.1/X521.2, S5.0)
[1] = AI 1 (X521.3/X521.4, S5.1)
p4097[0...1] TM31 analog inputs simulation mode / TM31 AI sim_mode
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: Integer16 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
0 1 0
p4098[0...1] TB30 analog inputs simulation mode setpoint / TB30 AI sim setp
TB30 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9104
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-11.000 [V] 11.000 [V] 0.000 [V]
p4098[0...1] TM31 analog inputs simulation mode setpoint / TM31 AI sim setp
TM31 Can be changed: U, T Calculated: - Access level: 2
Data type: FloatingPoint32 Dyn. index: - Func. diagram: 9566, 9568
P-Group: Terminals Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
-20.000 20.000 0.000