2 Parameters
2.2 List of parameters
SINAMICS G130/G150
550 List Manual (LH2), 04/2014, A5E03263479A
Description: Sets the signal sources for the inputs of the OR logic operation.
Dependency: Refer to: r2817
Note: [0]: OR logic operation, input 1 --> the result is displayed in r2817.0.
[1]: OR logic operation, input 2 --> the result is displayed in r2817.0.
Description: Displays the result of the OR logic operation.
Dependency: Refer to: p2816
Description: Setting and connector output for a fixed percentage value.
Dependency: Refer to: p2901, r2902, p2930
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling of the main setpoint)
Description: Setting and connector output for a fixed percentage value.
Dependency: Refer to: p2900, p2930
Notice: A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
Note: The value can be used to interconnect a scaling function (e.g. scaling of the supplementary setpoint)
p2816[0...1] BI: OR logic operation inputs / OR inputs
VECTOR_G Can be changed: T Calculated: - Access level: 2
Data type: Unsigned32 / Binary Dyn. index: - Func. diagram: 2634
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - 0
r2817.0 CO/BO: OR logic operation result / OR result
VECTOR_G Can be changed: - Calculated: - Access level: 2
Data type: Unsigned32 Dyn. index: - Func. diagram: 2634
P-Group: Functions Units group: - Unit selection: -
Not for motor type: - Scaling: - Expert list: 1
Min Max Factory setting
- - -
Bit field: Bit Signal name 1 signal 0 signal FP
00 OR logic operation result Yes No -
p2900[0...n] CO: Fixed value 1 [%] / Fixed value 1 [%]
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 1021
P-Group: Free function blocks Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]
p2901[0...n] CO: Fixed value 2 [%] / Fixed value 2 [%]
VECTOR_G Can be changed: U, T Calculated: - Access level: 3
Data type: FloatingPoint32 Dyn. index: DDS, p0180 Func. diagram: 1021
P-Group: Free function blocks Units group: - Unit selection: -
Not for motor type: - Scaling: PERCENT Expert list: 1
Min Max Factory setting
-10000.00 [%] 10000.00 [%] 0.00 [%]